Skip to content
SolarSystemCalc

Solar Wire Size Calculator (AWG & mm²)

Size the cables between panels, charge controller, batteries and inverter. Enter the current, system voltage, one-way cable length and the voltage drop you can accept; the calculator returns the minimum cross-section and the next standard size in both mm² and AWG.

Your inputs

A

Watts ÷ volts. E.g. a 3,000 W inverter at 48 V ≈ 70 A (with 90% efficiency).

V
m

Distance from source to load (not the round trip).

%

3% is typical for solar branch circuits; use 1–2% for battery-to-inverter cables.

Results update instantly. Nothing is sent to a server.

Results

Recommended (metric)

10 mm²

2.19% drop

Recommended (AWG)

8 AWG

2.61% drop

Minimum cross-section

7.29 mm²

for voltage drop

Carrying 30 A at 48 V over a 10 m one-way run (DC, copper) with at most 3% voltage drop needs a conductor of at least 7.29 mm². The next standard sizes that also meet the 125% ampacity rule are 10 mm² (IEC) or 8 AWG (AWG). Protect the cable with a 40 A fuse or breaker.

  • Always follow your local electrical code (NEC, BS 7671, AS/NZS 3000, IEC 60364). Ampacity depends on insulation, temperature and bundling.
Result breakdown
Round-trip factor2 conductors (out and back)
Resistivitycopper0.0175 Ω·mm²/m
Minimum area for voltage drop7.29 mm²
Required ampacity (125%)37.5 A
Recommended IEC size57 A rated10 mm²
Voltage drop with IEC size1.05 V (2.19%)
Power loss with IEC size31.5 W
Recommended AWG size50 A rated8 AWG (8.37 mm²)
Voltage drop with AWG size1.25 V (2.61%)
Power loss with AWG size37.6 W
Fuse / breaker≥ 125% of continuous current40 A
How this is calculated

Formulas

Minimum cross-section
Area (mm²) = factor × ρ × length (m) × current ÷ (voltage × drop fraction)

factor = 2 for DC and single-phase AC, √3 for three-phase; ρ = 0.0175 Ω·mm²/m for copper, 0.0282 for aluminium.

Ampacity check
Wire rating ≥ 1.25 × continuous current
Chosen size
Smallest standard size that satisfies both the area and the ampacity rule
Actual voltage drop
Drop (V) = factor × ρ × length × current ÷ chosen area
Power loss
Loss (W) = drop (V) × current
Fuse
Next standard fuse ≥ 1.25 × current

Assumptions & limitations

  • Resistivity values include a moderate temperature allowance; hot roofs or conduits increase resistance further.
  • Ampacities are NEC 75 °C column values for AWG and typical IEC PVC values for metric sizes – derate for high ambient temperatures or bundled cables.
  • Length is the one-way distance; the calculator doubles it for the return conductor.
  • This tool is a planning aid, not a code-compliance check. A licensed electrician must verify the final design.

How the solar wire size calculator works

This tool finds the minimum cable size for a solar circuit — panel to charge controller, controller to battery, or battery to inverter — based on the current it will carry, the system voltage, the one-way cable length, and how much voltage drop you're willing to accept.

You enter:

  • Current (A) — the maximum current the circuit will carry
  • System voltage (V)
  • One-way cable length, with a toggle between metres and feet
  • Acceptable voltage drop — default 3 percent for DC solar runs, 2 percent for battery-to-inverter cabling
  • Conductor material — copper (default) or aluminium
  • Circuit type — DC or AC single-phase (round-trip factor of 2), or AC three-phase (factor of 1.732)

The math, in plain terms

The core formula is:

Minimum cross-section (mm²) = (factor × resistivity × one-way length in metres × current) ÷ (voltage × drop fraction)

Where:

  • factor is 2 for DC or single-phase AC (current travels out and back), or 1.732 (√3) for three-phase AC
  • resistivity is 0.0175 ohm·mm²/m for copper, or 0.0282 ohm·mm²/m for aluminium
  • drop fraction is your acceptable percentage expressed as a decimal (3 percent = 0.03)

Once the minimum cross-section is known, the calculator rounds up to:

  • The next standard IEC metric size: 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, or 120 mm²
  • The next standard AWG size: 14, 12, 10, 8, 6, 4, 2, 1/0, 2/0, 3/0, or 4/0

It then cross-checks that size against a simplified ampacity table to confirm it can safely carry 125 percent of your entered current, accounting for the continuous-duty derating solar circuits need since they can run near full output for hours. Finally, it reports the actual voltage drop and power loss (in watts) for the selected wire.

Why voltage drop matters more at low voltage

Voltage drop is driven by current, not power, and current rises sharply as system voltage falls for the same wattage. A 1,000 W load draws about 83 A at 12 V but only about 21 A at 48 V — four times less. A fixed percentage drop at 12 V is a smaller absolute voltage cushion (0.36 V at 3 percent) than at 48 V (1.44 V at 3 percent), so low-voltage systems need noticeably thicker cable, shorter runs, or both to stay within the same percentage loss.

The 3 percent rule of thumb

Three percent is a widely used target for DC solar wiring because it balances cable cost against energy loss. Tighter than that means oversized, expensive cable for little practical gain, while looser than 3 percent noticeably reduces charging efficiency and can cause controllers or inverters to misread battery voltage. Battery-to-inverter runs often use a tighter 2 percent limit since they carry the highest current in the system.

AWG to mm² conversion

AWGApprox. mm²AWGApprox. mm²
142.5425
124235
1061/050
8102/070
6163/095

These are close approximations for comparing standards — check the exact ampacity on a manufacturer's chart before finalizing.

Typical wire sizes for common runs

RunTypical voltageTypical currentCommon wire size range
Panel to charge controller12–48 V5–15 A4–10 mm² (AWG 12–8)
Controller to battery (short run)12 V20–40 A10–16 mm² (AWG 8–4)
Controller to battery (short run)48 V20–40 A4–6 mm² (AWG 10–8)
Battery to inverter12 V80–150 A35–70 mm² (AWG 2–2/0)
Battery to inverter48 V20–40 A6–16 mm² (AWG 8–4)

Exact figures depend on your actual current draw and cable length — run your own numbers through the calculator rather than relying on this table alone.

Ampacity and voltage drop both have to pass

These are two separate checks, and a wire has to satisfy both. Ampacity is about heat — a wire carrying more current than it's rated for gets hot enough to damage insulation or start a fire. Voltage drop is about efficiency and equipment behaviour — a wire that's ampacity-safe can still be too thin if the run is long, wasting power and starving equipment of voltage. On short runs, ampacity is usually the limiting factor. On long runs, especially in 12 V systems, voltage drop often forces a larger size than ampacity alone would require.

Fuse and breaker sizing

The fuse or breaker's job is to protect the wire, not the device at the end of it. Size overcurrent protection at about 125 percent of the expected continuous current, and never larger than the wire's rated ampacity. If you upsize the wire for voltage drop, keep the fuse or breaker sized to the actual current draw, not to the wire's higher ampacity capability.

PV wire types

Outdoor solar cable is usually a different product from standard indoor building wire — look for cable rated for UV exposure, temperature extremes, and often double insulation, commonly labelled PV1-F or H1Z2Z2-K in Europe, or USE-2 / PV wire in North America. Indoor runs can generally use standard building or battery cable rated for the environment and current involved.

Local codes take precedence

This calculator gives an engineering estimate, not a compliance check. Electrical codes vary by country — NEC in the United States, BS 7671 in the United Kingdom, AS/NZS 3000 in Australia, and national IEC adaptations elsewhere — and can mandate specific minimum sizes, derating factors, conduit fill limits, or grounding requirements beyond this simplified calculation. Confirm your final wire choice against the code in your location, and consult a licensed electrician for anything permanent or safety-critical.

Related calculators

Frequently asked questions

What wire size do I need for a 12 volt solar system?

It depends heavily on current and cable length, but as an example, a 20 A, 5 metre (16 ft) one-way run at 12 V and 3 percent drop typically needs around 6 mm² or AWG 10 copper cable; always confirm with the calculator using your own numbers.

Why does voltage drop matter more on 12 V systems than 48 V systems?

The same wattage draws four times more current at 12 V than at 48 V, and voltage drop is driven by current, so low-voltage systems need proportionally thicker cable to keep the percentage loss acceptable.

What is the standard voltage drop limit for solar wiring?

A common rule of thumb is 3 percent maximum drop for DC runs like panel-to-controller or controller-to-battery, and a tighter 2 percent for battery-to-inverter cabling since that run often carries the highest current in the system.

Should I size a wire by voltage drop or by ampacity?

Both must be checked and you use whichever gives the larger wire. Ampacity ensures the wire doesn't overheat carrying the current; voltage drop ensures you aren't wasting significant power and that connected equipment sees adequate voltage.

How should a fuse or breaker be sized relative to the wire?

The fuse or breaker protects the wire, not the appliance, so it should be sized at about 125 percent of the expected continuous current but never above the wire's safe ampacity rating.

What type of cable should I use for outdoor solar panel wiring?

Look for cable rated for outdoor, UV-resistant, and often double-insulated use, commonly labelled PV1-F, USE-2, or H1Z2Z2-K depending on your region, rather than standard indoor building wire.

Do I need copper or can I use aluminium wire for solar?

Copper is standard for most solar DC wiring because it has lower resistance and connects more reliably to conventional lugs; aluminium is sometimes used for long AC runs to cut cost, but it needs a larger cross-section and connectors rated for aluminium.